| Sign In | Join Free | My autochinanet.com |
|
Brand Name : Fenigal
Model Number : Fenigal
Certification : CE
Place of Origin : china
MOQ : 1 pc
Payment Terms : T/T, Western Union
Supply Ability : 60000 Unit/Units per Month
Delivery Time : 5-8 working days
Packaging Details : standard export packing
Operation : -5~40℃
Storage and transport : -25~55℃
Rated operation voltage (V) : Ue AC50Hz
Ultimate breaking capacity : Icu AC50Hz 220/240V
(kA effective value) : 380/415V
Electrical endurance : AC50Hz 440V-In
Class CB Automatic Transfer Switch with Overcurrent Release and Rated Current WATSN-800
Class CB
ATSE with overcurrent release
Its main contact can be closed and used to break short-circuit current
WATSN series automatic transfer switch is a class CB automatic transfer switch if it
adopts a circuit breaker with overcurrent release as the actuator. With selective
protective function, it can provide short-circuit and overload protection for
downstream loads and cables. Its making and breaking capacity is significantly
higher than other components such as contactors and relays.
| Model and specification Electrical characteristics determined according to IEC 60947-6-1&GB14048.11 |
WATSN-800 | WATSN-1000 | WATSN-1250 | WATSN-1600 | |||
| Number of poles | 34 | 3,4 | 34 | 34 | |||
| Controller | |||||||
| Type A | ■ | ■ | ■ | ■ | |||
| Type B | ■ | ■ | ■ | ||||
| Type D | |||||||
| Actuation component | NS-N,NS-H | ||||||
| Rated current (A) | In | 800 | 1000 | 1250 | 1600 | ||
| Rated insulation voltage V) | Ui | 800 | 800 | 800 | 800 | ||
| Rated impulse withstand voltage (kV) | Uimf | 8 | 8 | 8 | 8 | ||
| Rated operation vottage (V) | Ue | AC50Hz | 415 | 415 | 415 | 415 | |
| Ultimate breaking capacity | Icu | AC50Hz | 220/240V | 50/70 | 50/70 | 50/70 | 50/70 |
| (kA effective value) | 380/415V | 50/70 | 50/70 | 50/70 | 50/70 | ||
| Operation breaking capacity | Ics | (%lcu) | 75% | 75% | 75% | 75% | |
| Isolation function | ■ | ■ | ■ | ■ | |||
| Mechanical endurance | (“) | 10000 | 10000 | 10000 | 10000 | ||
| Electrical endurance | (“) | AC50Hz 440V-In | 5000 | 5000 | 4000 | 2000 | |
| Minimum contact transfer time | (**) | S | 2.5 | 2.5 | 2.5 | 2.5 | |
| Protection and measurement | |||||||
| Interchangeable control unit | Common release (standard) | Mic2.0 | Mic2.0 | Mic2.0 | Mic2.0 | ||
| Common release (standard) | Mic5.0 | Mic5.0 | Mic5.0 | Mic5.0 | |||
| Installation and connection | |||||||
| Fixation /Panel front connection | (***) | ■ | ■ | ■ | |||
| Monitoring and indication auxiliary device | |||||||
| Position feedback signal | ■ | ■ | ■ | ||||
| Fire protection linkage function | ■ | ■ | ■ | ||||
| Alarm feedback signal | ■ | ■ | ■ | ||||
|
|
Class CB Automatic Transfer Switch with Overcurrent Release and Rated Current WATSN-800 Images |